How to Preform the Worcester Greenstar Fan Pressure Test
This page is dedicated to performing the Worcester Greenstar Fan Pressure Test. This test is to determine if the heat exchanger requires cleaning or attention.
The information published on this page only applies to the following range of boilers:
Natural Gas:
- Greenstar 9i System ErP. GC Number: 41-406-21
- Greenstar 12i System ErP. GC Number: 41-406-23
- Greenstar 15i System ErP. GC Number: 41-406-25
- Greenstar 18i System ErP. GC Number: 41-406-27
- Greenstar 21i System ErP. GC Number: 41-406-29
- Greenstar 24i System ErP. GC Number: 41-406-31
LPG:
- Greenstar 9i System ErP. GC Number: 41-406-22
- Greenstar 12i System ErP. GC Number: 41-406-24
- Greenstar 15i System ErP. GC Number: 41-406-26
- Greenstar 18i System ErP. GC Number: 41-406-28
- Greenstar 21i System ErP. GC Number: 41-406-30
- Greenstar 24i System ErP. GC Number: 41-406-32
How to Reset the Service Reminder Function
Setting the appliance to minimum or maximum mode when the service reminder function is active, a service reminder reset notification is displayed h13/H13.
How to reset the service reminder value in boiler settings menu:
- Press the back arrow/spanner button and tick button for approximately 5 seconds to enter appliance menu.
- Use the DHW up and DHW down buttons to scroll through the boiler settings.
- Press the tick button to select “info menu”.
- Use the DHW up and DHW down buttons to scroll through the menu.
- Press the tick button to select “2.5F” – service reminder time.
- Range from 0-72 months (0 = off). Press the tick button to confirm.
- Press the back arrow / spanner button to leave info menu.
Starting the Worcester Greenstar fan pressure test
Set the appliance to maximum rate.
Set the appliance to maximum output by pressing the chimney sweep button for at least 5 seconds.
The chimney sweep symbol will be displayed at the top of the screen and the word “Max” will flash at the bottom of the screen. The appliance will ramp up to maximum output in 30 to 35 seconds. Ensure that the appliance has stabilised at maximum output.
When running at maximum output, and the water temperature is 65°C or less, the appliance will operate both the central heating and DHW circuits with the diverter valve in the mid position. It will be necessary to run sufficient water through the DHW circuit to ensure that the appliance will not cycle on low heating demands. This is to allow sufficient time for the setting procedure. When the water temperature reaches 75°C the diverter valve will switch to CH only.
Connect the tubing from a digital manometer to the fan pressure test point.
The fan pressure will read negative value.
Natural Gas Appliances:
- 9i system boiler: Clean Heat Exchanger < -5.0mb =< Heat Exchanger OK
- 12i system boiler: Clean Heat Exchanger < -8.6mb =< Heat Exchanger OK
- 15i system boiler: Clean Heat Exchanger < -4.8mb =< Heat Exchanger OK
- 18i system boiler: Clean Heat Exchanger < -7.0mb =< Heat Exchanger OK
- 21i system boiler: Clean Heat Exchanger < -3.4mb =< Heat Exchanger OK
- 24i system boiler: Clean Heat Exchanger < -4.2mb =< Heat Exchanger OK
LPG Appliances:
- 9i system boiler: Clean Heat Exchanger < -5.3mb =< Heat Exchanger OK
- 12i system boiler: Clean Heat Exchanger < -9.8mb =< Heat Exchanger OK
- 15i system boiler: Clean Heat Exchanger < -5.4mb =< Heat Exchanger OK
- 18i system boiler: Clean Heat Exchanger < -7.9mb =< Heat Exchanger OK
- 21i system boiler: Clean Heat Exchanger < -3.8mb =< Heat Exchanger OK
- 24i system boiler: Clean Heat Exchanger < -4.7mb =< Heat Exchanger OK
After completing your fan pressure test:
- If during the fan test your manometer reading indicates the heat exchanger needs cleaning, then carry out the following checks:
– Check that the siphon is not blocked.
– Check the exhaust paths for restrictions.
– Clean the heat exchanger with a suitable cleaning tool, refer to section 7.6 – Cleaning the heat exchanger. - Re-check the fan pressure readings.
If the appliance, after completing the above checks, fails the fan pressure test then contact Worcester, Bosch Group for advice. - After the measurements are taken switch the appliance off.
- Disconnect the manometer and replace the test point cover.
- Replace the combustion air intake pipe.
If you’re based in Lincolnshire and you’d like to book an iWarm gas engineer for your Worcester Greenstar boiler service, use the contact form or call us on 07825 121000.
Other pages which might interest you:
Worcester Greenstar Fan Pressure Test
EXCELLENT
Based on 8 reviews
Posted on Google
James6 October 2026Trustindex verifies that the original source of the review is Google.
Great service, quick booking and visit. Sent the certs same day. Recommended.Posted on Google
Samara6 July 2026Trustindex verifies that the original source of the review is Google.
Great service, reasonable pricing, got the job done extremely quick, nice lad, very professional and cleaned up after himself, absolutely would recommendPosted on Google
Dainora27 May 2026Trustindex verifies that the original source of the review is Google.
I had a boiler issue, stopped working. He arrived on the same day and ensured that the boiler works while we wait for parts. Kept me updated while parts were coming and asked if the boiler is still working. Always kept the area clean and explained what was the issue. Great job! Definitely recommend.Posted on Google
Adrian18 May 2026Trustindex verifies that the original source of the review is Google.
Fantastic service from Guy, who travelled out to Market Rasen on a Sunday when our boiler stopped working. He was super professional, quick to sort the issue, and great value for money. With kids in the house, getting the heating and hot water back on meant everything, definitely one of those luxuries you take for granted until they’re gone. Really appreciate the effort and would highly recommend.Posted on Google
Annette29 March 2026Trustindex verifies that the original source of the review is Google.
Guy came to us today which was a wet and cold Sunday afternoon as my Elderly Mother was without heating. After initial contact a time was agreed and Guy arrived on the dot.... He was very good and explained everything he was doing ensuring we understood what was happening. Guy was very clean and there was not a single bit of mess left behind. He made sure we were happy with the work and didnt leave until he was 100% sure the problem was fixed. There was no hard sell with Guy at all he explained a few options for us in the future. Would HIGHLY reccommend Guy and have saved his details for future use. 5☆☆☆☆☆Posted on Google
David20 March 2026Trustindex verifies that the original source of the review is Google.
Thank you very much for servicing my boiler and balancing my radiators. All working well again. Highly recommended.Posted on Google
James10 March 2026Trustindex verifies that the original source of the review is Google.
Was polite and tidy. Fixed an issue with our central heating and fitted a new bathroom radiator. Thanks
Questions? Contact us
Serving customers in Grimsby, Cleethorpes, Immingham, Louth, Brigg, Caistor, Market Rasen, Barton upon Humber and Scunthorpe.